1.6.5.2 One exterior door
Door
In-room Event
(Motion/
Thermostat Key Pressed/
Deadbolt Engaged)
HVAC
State
Closed
Yes
Per guest setting
Occupied
Open
Yes
OFF (20 seconds or
standard unoccupied
time)
Unoccupied or Unsold
Closed
No
Setback
Unoccupied or Unsold
Open
No
OFF (20 seconds or
standard unoccupied
time)
Unoccupied or Unsold
Table 3
1.6.5.3 One exterior and one interior door
Interior Door
Exterior Door
Motion
HVAC
State
Closed
Closed
Yes
Per guest setting
Occupied
Open
Closed
Yes
Per guest setting
Unoccupied or Unsold
Closed
Open
Yes
OFF
Unoccupied or unsold
Open
Open
Yes
OFF
Unoccupied or Unsold
Closed
Closed
No
Setback
Unoccupied or Unsold
Open
Closed
No
Setback
Unoccupied or Unsold
Closed
Open
No
OFF
Unoccupied or Unsold
Open
Open
No
OFF
Unoccupied or Unsold
Table 4