At Tools/Options, there is a tab for Energy management, in turn containing the
tabs General, Maintenance and Housekeeping.
8.1 General
At Tools/Options/Energy management/General, the below parameters can be
modified; enter the applicable value(s) and click OK:
1. Enable energy management: This checkbox is automatically marked when the
Orion EMS option is set in the Visionline software. If the Orion EMS option should
temporarily be turned off, unmark 'Enable energy management' and click OK.
2. Staff entry allow room occupancy change: If this checkbox is marked, the room
will go to occupied state when motion is triggered if staff is in the room, i.e. when
a staff card has opened the room.
3. Max HVAC runtime: An alarm is triggered if a HVAC runs this long without
reaching the set temperature, i.e. the temperature which the guest has set
on the thermostat. Default is 120 minutes; the valid range is 30-300 minutes.
4. Max setback override: The setback override cannot exceed the number of hours
specified here; the valid range for ‘Max setback override’ is 0-99 hours. If the