Line Function Setting range
or display
Setting
increment
Basic
setting
6201 S Reset sensors No, Yes No
6205 S Reset to default parameters No, Yes No
6220 S Software version (RVS) 0... 99 --
6300 S Info 1 OEM 0... 65535 --
6301 S Info 2 OEM 0... 65535 --
LPB system
6600 S Device address 0... 16 1
Error
6711 U Reset HP No, Yes No
6800 S History 1 Time, Date, Error code
6802 S History 2 Time, Date, Error code
6804 S History 3 Time, Date, Error code
6806 S History 4 Time, Date, Error code
6808 S History 5 Time, Date, Error code
6810 S History 6 Time, Date, Error code
6812 S History 7 Time, Date, Error code
6814 S History 8 Time, Date, Error code
6816 S History 9 Time, Date, Error code
6818 S History 10 Time, Date, Error code
Maintenance / special regime
7070 S HP interval --, 1... 240 1 month --
7071 S HP time since maint
Reset ? (no, yes)
0... 240 1 month 0
7073 S Cur starts compr1/hrs run (since the 6 last weeks)
Reset ? (no, yes)
0... 12 0
7141 U Emergency operation Off, On Off
Off: Heat pump functions normally (with boosters if necessary).
On: Heat pump uses the electric boost system or the boiler connection.
Use the “On” position only in Assist mode or Test mode: may result in high power bills.
7142 S Emergency operating function type Manual, Automatic Manual
Manual: Emergency mode is not active when a fault occurs (Emergency mode = OFF).
Automatic: Emergency mode is active when a fault occurs (Emergency mode = ON).
In "Automatic" position, the energy cost can be onerous if the error is not detected and eliminated.
7150 I Simulation outdoor temp -50... 50 °C 0,5 --
Installation and operation manual "1734 - EN"
Heat pump air/water split 1 service alféa extensa +
- 62 -