- 37 -
4.3.3 Stopping
To stop the unit , proceed as follows:
Switch off the load.
Switch off circuit breaker Q1.
Stop the engine by using the STOP button on the
Qc2002™ module.
Put the starter switch S20 in position O (OFF) to
shut down the voltage apply towards the
Qc2002™ module.
Lock all doors to avoid unauthorized access.
To stop the unit when the Qc2002™ module is in
AUTOMATIC operation mode, proceed as
follows:
Switch off the load.
For remote start:
When operating in Island mode, use the
external switch to stop the machine.
When operating in AMF mode, the machine
will automatically stop when the Mains
returns.
Cooldown period default 15 sec.
Put the starter switch S20 in position O (OFF) to
shut down the voltage apply towards the
Qc2002™ module.
Lock all doors to avoid unauthorized access.
4.3.4 Setting the Qc2002
4.3.4.1 Pushbutton and LED functions
Following pushbuttons are used on the
Qc2002™:
When the unit is stopped with the
STOP button in Automatic
operation, it will automatically go to
Manual Mode.
1
ENTER: Is used to select and
confirm changed settings in the
Parameter list.
2
UP: Is used to scroll through the
display information and to adjust
parameter value upwards.
3
DOWN: Is used to scroll through the
display information and to adjust
parameter value downwards.
4BACK: Is used to leave the Alarm
pop-up window, to leave the
Parameter list and to leave menu's
without change.
Qc2002 CAN
v x.xx.xx
G
6
5
8
93
1
2
4
7

Table of Contents