- 81 -
6 Checks and trouble
shooting
6.1 Checks
6.1.1 Checking voltmeter P4
– Put a voltmeter in parallel with voltmeter P4 on
the control panel.
– Check that the read-out of both voltmeters is the
same.
– Stop the generator and disconnect one terminal.
– Check that the internal resistance of the voltmeter
is high.
6.1.2 Checking ammeters P1, P2 and
P3
– Measure the outgoing current during the load, by
means of a clamp-on probe.
– Compare the measured current with the current
indicated on ammeter. Both readings should be
the same.
6.2 Engine troubleshooting
Refer to the engine’s operator manual for the engine
troubleshooting. An extensive Engine
troubleshooting manual is available at Volvo Penta.
For more information contact Volvo Penta.
Never perform a test run with
connected power cables. Never
touch an electrical connector
without a voltage check.
When a failure occurs, always
report what you experienced before,
during and after the failure.
Information with regard to the load
(type, size, power factor, etc.),
vibrations, exhaust gas colour,
insulation check, odours, output
voltage, leaks and damaged parts,
ambient temperature, daily and
normal maintenance and altitude
might be helpful to quickly locate
the problem. Also report any
information regarding the humidity
and location of the generator (e.g.
close to sea).