Cable installation in ac-
cordance with EMC
Signal and fieldbus cables are susceptible to interference. Motor cables are
interference sources.
●
Lay cables being susceptible to interference or sources of interference at the
highest possible distance from each other.
●
The interference immunity of signal and fieldbus cables increases if the cables
are laid close to the earth potential.
●
If possible, avoid laying long cables and make sure that they are installed in
areas being subject to low interference.
●
Avoid parallel paths with little cable distance of cables being either susceptible
to interference or interference sources.
6.2. S/SH electrical connection (AUMA plug/socket connector)
Figure 17: S and SH electrical connection
[1] Cover
[2] Socket carrier with screw-type terminals
Short description
Plug-in electrical connection with screw-type terminals for power and control contacts.
Control contacts also available as crimp-type connection as an option.
S version (standard) with three cable entries. SH version (enlarged) with additional
cable entries. For cable connection, remove the AUMA plug/socket connector and
the socket carrier from cover.
Technical data
Table 13:
Electrical connection via AUMA plug/socket connector
Control contactsPower contacts
50 pins/sockets6 (3 equipped) + protective
earth conductor (PE)
No. of contacts max.
1 to 50U1, V1, W1, U2, V2, W2, PEDesignation
250 V750 VConnection voltage max.
16 A25 ARated current max.
Screw connection, crimp-type (option)Screw connectionType of customer connection
2.5 mm
2
(flexible or solid)
6 mm
2
(flexible)
10 mm
2
(solid)
Connection diameter max.
23
SQ 05.2 – SQ 14.2/SQR 05.2 – SQR 14.2 Control unit: electronic (MWG)
AC 01.2 Non-Intrusive Electrical connection