AUMA SA 07.2 - 12.3.2. Fuse replacement; 12.3.2.1. Replace fuses F1;F2; 12.3.2.2. Test;replace fuses F3;F4

AUMA SA 07.2
96 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Commands and signals of the Modbus RTU interface
OPEN, STOP, CLOSE, position setpoint, RESET, EMERGENCY operation command, enable LOCAL,
Interlock OPEN/CLOSE
Process representation output
(command signals)
End positions OPEN, CLOSED
Actual position value
Actual torque value, requires MWG in actuator
Selector switch in position LOCAL/REMOTE
Running indication (directional)
Torque switches OPEN, CLOSED
Limit switches OPEN, CLOSED
Manual operation by handwheel or via local controls
Analogue (2) and digital (4) customer inputs
Process representation input (feed-
back signals)
Motor protection tripped
Torque switch tripped in mid-travel
One phase missing
Failure of analogue customer inputs
Process representation input (fault
signals)
The behaviour of the actuator is programmable:
Stop in current position
Travel to end position OPEN or CLOSED
Travel to any intermediate position
Execute last received operation command
Behaviour on loss of communication
Service conditions
Indoor and outdoor use permissibleUse
Any positionMounting position
2 000 m above sea level
> 2,000 m above sea level, on request
Installation altitude
Refer to name plate of actuator controlsAmbient temperature
Up to 100 % relative humidity across the entire permissible temperature rangeHumidity
IP68Standard:Enclosure protection in accordance
with IEC 60529
Terminal compartment additionally sealed against interior of actuator controls (double
sealed)
Option:
According to AUMA definition, enclosure protection IP68 meets the following requirements:
Depth of water: Maximum 8 m head of water
Continuous immersion in water: maximal 96 hours
Up to 10 operations during immersion
Modulating duty is not possible during immersion.
For exact version, refer to actuator controls name plate.
Pollution degree 4 (when closed), pollution degree 2 (internal)Pollution degree according to
IEC 60664-1
1 g, from 10 Hz to 200 Hz
Resistant to vibration during start-up or for failures of the plant. However, a fatigue strength may not be
derived from this. (Not valid in combination with gearboxes)
Vibration resistance according to
IEC 60068-2-6
KS: Suitable for use in areas with high salinity, almost permanent condensation, and high
pollution.
Standard:Corrosion protection
KX: Suitable for use in areas with extremely high salinity, permanent condensation, and
high pollution.
Option:
Double layer powder coating
Two-component iron-mica combination
Coating
AUMA silver-grey (similar to RAL 7037)Standard:Colour
Available colours on requestOption:
86
SA 07.2 SA 16.2/SAR 07.2 SAR 16.2 Control unit - electromechanical
Technical data AC 01.2 Intrusive Modbus RTU