Accessories
For actuator controls mounted separately from the actuator, including plug/socket connector.
Connecting cable on request.
Recommended for high ambient temperatures, difficult access, or in case of heavy vibration during
service.
Cable length between actuator and actuator controls is max. 100 m. An MWG is required for position
feedback.
Wall bracket
AUMA CDT (Commissioning and Diagnostic Tool for Windows-based PC)
AUMA Assistant App (Commissioning and Diagnostic Tool for Android devices)
Programming software
Accessory for torque measurement for SA/SAR 07.2 – SA/SAR 16.2Torque measurement flange DMF
Further information
Approx. 7 kg (with AUMA plug/socket connector)Weight
Machinery Directive 2006/42/EC
Low Voltage Directive 2014/35/EU
EMC Directive 2014/30/EU
RoHS Directive 2011/65/EU
EU Directives
14.3. Tightening torques for screws
Table 42:
Tightening torques for screws
Tightening torque [Nm]Threads
Strength class
A2-80/A4-80A2-70/A4-70
107.4M6
2418M8
4836M10
8261M12
200150M16
392294M20
1,0571,015M30
2,1211,769M36
87
SA 07.2 – SA 16.2/SAR 07.2 – SAR 16.2 Control unit - electromechanical
AC 01.2 Intrusive Modbus RTU Technical data