2. Operate actuator using push buttons OPEN, STOP, CLOSE.
➥
The limit switching is set correctly if (default indication):
- the yellow indication light/LED1 is illuminated in end position CLOSED
- the green indication light/LED5 is illuminated in end position OPEN
- the indication lights go out after travelling into opposite direction.
➥
The limit switching is set incorrectly if:
- the actuator comes to a standstill before reaching the end position
- one of the red indication lights/LEDs is illuminated (torque fault)
-
the status indication S0007 in the display signals a fault.
3. If the end position setting is incorrect: Reset limit switching.
10.6.4. Reference operation position feedback: perform
For actuators with position feedback (RWG, potentiometer), a reference operation
has to be performed once the limit switching setting was changed to ensure that the
position feedback (0/4 – 20 mA) supplies correct values:
→
Operate actuator electrically (via the push buttons OPEN and CLOSE of the
local controls) once to end position OPEN and once to end position CLOSED.
10.7. Close switch compartment
✔
If options (e.g. potentiometer, position transmitter) are available: Only close switch
compartment once all optional equipment has been successfully set.
Corrosion due to damage to paint finish
→
Touch up damage to paint finish after work on the device.
1. Clean sealing faces of housing and cover.
2. Preserve joint surfaces with an acid-free corrosion protection agent.
3. Check whether O-ring [3] is in good condition, replace if damaged.
4. Apply a thin film of non-acidic grease (e.g. petroleum jelly) to the O-ring and
insert it correctly.
Figure 69:
64
SAEx 07.2 – SAEx 16.2/SAREx 07.2 – SAREx 16.2 Control unit - electromechanical
Commissioning (basic settings) ACExC 01.2 Intrusive Profinet