EasyManuals Logo

AUMA SQ 05.2 Operation Instructions

AUMA SQ 05.2
108 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #70 background imageLoading...
Page #70 background image
2. Connect ammeter for 0 20 mA to measuring points [4 and 5].
3. Turn potentiometer [1] clockwise to the stop.
4. Turn potentiometer [1] slightly in opposite direction.
5. Turn potentiometer [2] clockwise until output current starts to increase.
6. Turn potentiometer [2] in opposite direction until the following value is reached:
- for 0 20 mA approx. 0.1 mA
- for 4 20 mA approx. 4.1 mA
This ensures that the signal remains above the dead and live zero point.
7. Move valve to end position OPEN.
8. Set potentiometer [3] to end value 20 mA.
9. Approach end position CLOSED again and check minimum value (0.1 mA or
4.1 mA). If necessary, correct the setting.
70
SQEx 05.2 SQEx 14.2 / SQREx 05.2 SQREx 14.2 Control unit - electromechanical
Commissioning (optional equipment settings) ACExC 01.2 Intrusive

Table of Contents

Other manuals for AUMA SQ 05.2

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the AUMA SQ 05.2 and is the answer not in the manual?

AUMA SQ 05.2 Specifications

General IconGeneral
BrandAUMA
ModelSQ 05.2
CategoryController
LanguageEnglish

Related product manuals