EasyManuals Logo

Automationdirect.com GS1-10P5 User Manual

Default Icon
137 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #86 background imageLoading...
Page #86 background image
Transmission Fault Treatment Mem Addr 0903H(42308)
Default Setting: 0
Setting: 0 - Display fault and continue operating
1 - Display fault and RAMP to stop
2 - Display fault and COAST to stop
3 - No fault displayed and continue operating
Time Out Detection Mem Addr 0904H(42309)
Range: 0 - Disable Default Setting: 0
1 - Enable
•This parameter is used for ASCII mode. When this parameter is set to
01, it indicates that the over-time detection is enabled and the time slot between
each character cannot exceed 500 ms.
Time Out Duration Mem Addr 0905H(42310)
Range: 0.1 to 60.0 seconds Default Setting: 0.5
Parameter Lock Mem Addr 0907H(42312)
Range: 0 - All parameters can be set and read Default setting: 0
1 - All parameters are read-only
Restore to Default Mem Addr 0908H(42313)
Range: 0 to 99 Default Setting: 0
• Setting 99 restores all parameters to factory defaults.
Block Transfer Parameter 1 Mem Addr 090BH(42316)
Range: 0-00 to 8-01, and 9-99 Default Setting: 9-99
• Setting 9-99 disables the parameter.
Block Transfer Parameter 2 Mem Addr 090CH(42317)
Range: 0-00 to 8-01, and 9-99 Default Setting: 9-99
• Setting 9-99 disables the parameter.
9-12
9-11
9-08
9-07
9-05
9-04
9-03
GS1 Series AC Drive User Manual
4–47
Chapter 4: AC Drive Parameters

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Automationdirect.com GS1-10P5 and is the answer not in the manual?

Automationdirect.com GS1-10P5 Specifications

General IconGeneral
BrandAutomationdirect.com
ModelGS1-10P5
CategoryController
LanguageEnglish

Related product manuals