RS485 Speed Reference Mem Addr 091AH(42331)
Range: 0.0 to 400.0 Hz Default Setting: 60.0
This parameter is used to set the Master Frequency when the AC drive is
controlled by communication interface.
RUN Command Mem Addr 091BH(42332)
Range: 0 - Stop Default Setting: 0
1 - Run
Direction Command Mem Addr 091CH(42333)
Range: 0 - Forward Default Setting: 0
1 - Reverse
External Fault Mem Addr 091DH(42334)
Range: 0 - No fault Default Setting: 0
1 - External fault
Fault Reset Mem Addr 091EH(42335)
Range: 0 - No action Default Setting: 0
1 - Fault Reset
JOG Command Mem Addr 091FH(42336)
Range: 0 - Stop Default Setting: 0
1 - Jog
9-31
9-30
9-29
9-28
9-27
9-26
GS1 Series AC Drive User Manual