Frequency Command F (XXX.X) Memory Address 2102H(48451)
Status location for the frequency setting of the AC drive.
Output Frequency H (XXX.X) Memory Address 2103H(48452)
Status location for the actual operating frequency present at the T1, T2, and T3 terminals
Output Current A (XXX.X) Memory Address 2104H(48453)
Status location for the output current present at the T1, T2, and T3 terminals.
DC-BUS Voltage d (XXX.X) Memory Address 2105H(48454)
Status location for the DC Bus Voltage.
Output Voltage U (XXX.X) Memory Address 2106H(48455)
Status location for the output voltage present at the T1, T2, and T3 terminals.
Motor RPM Memory Address 2107H(48456)
Status location for the present estimated speed of the motor
Scale Frequency (Low word) Memory Address 2108H(48457)
Status location for result of output frequency x 8-01 (low word).
Scale Frequency (High word) Memory Address 2109H(48458)
Status location for result of output frequency x 8-01 (high word).
% Load Memory Address 210BH(48460)
Status location for the amount of load on the AC drive. (Output Current ÷ Drive
Rated Current) x 100
Firmware Version Memory Address 2110H(48465)
GS1 Series AC Drive User Manual
5–5
Chapter 5: GS1 MODBUS Communications