KRN100
Series
A-10
Record zone division [ Divide Zone ]
File/Memory setup [ FILE/MEMORY SETUP ]
Standard record period [ Standard Period ]
Summer time [ Summer Time ]
Reservation record [ Reservation Type ]
Divides•record•zone•for•measuring•value•by•channel.•
It•divides•equally•max.•12•zones•as•equal•value.•User•
needs•to•set•record•zone•by•channel•in•Record•Zone•
setting•at•Input•Setup.•
It•is•easy•to•check•measuring•value•due•not•to•duplicated•
record•zone•with•divided•record•zone•by•channel•which•is•
set•in•Record•Zone•setting•at•Input•Setup.
If•there•is•too•many•division•for•record•zone,•record•value•
check•accuracy•is•low.•
•
•
•Set•range:•None,•2•to•12
•
•
Factory•default:•None
You•can•set•the•parameter•about•parameter•set•le•and•
storage•data.•Move•to•FILE/MEMORY•SETUP•with•the•
,• ••keys•,•press•the• •key•to•enter•FILE/
MEMORY•SETUP.
Set•record•period•to•record•current•time,•display•value•by•
channel•as•digital•number•on•recording•paper.
It•is•activated•when•Record•Mode(Record•mode)•is•Digital.
•
•
•Set•range:•00m•01s•to•99m•59s
• Depending•on•the•number•of•recording•channels,•min.•
set•range•is•limited•as•below.
•
•
•Factory•default:•-
Record•channel Set•range
1•to•2 01m•00s•to•99m•59s
3•to•4 02m•00s•to•99m•59s
5•to•6 03m•00s•to•99m•59s
7•to•8 04m•00s•to•99m•59s
9•to•10 05m•00s•to•99m•59s
11•to•12 06m•00s•to•99m•59s
This•function•is•for•applying•summer•time•(daylight•saving•
time)•in•specic•countries•and•regions.
When•you•set•Summer•Time,•it•adds•current•time•and•1•
hour•and•displays•the
「
(S)
」
mark•in•front•of•the•date•and•
time•on•LCD•screen•or•in•front•of•the•date•on•recording•
paper.•
•
•
•Set•range:•Disable•↔•Enable
•
•
•Factory•default:•Disable
This•function•is•to•set•reservation•time.•At•the•set•time,•it•
starts/stops•recording•automatically.•
You•can•select•reservation•record•either•Repeat(repeat•
ON/OFF)•or•Single(single•ON/OFF).
When•selecting•reservation•record,•‘Reservation•
Period(Reservation•record•period)’•and••‘Reservation•
Time(Reservation•record•time)’•are•activated.•When•
reservation•record•is•set,•the• •icon•ashes•with•the•
(recording)•or•the•
•(stop•recording)•icon.
The• •icon•tuns•OFF•when•reservation•setting•is•‘Disable’.
•
•
Set•range:•Disable•↔•Repeat•↔•Single
•
•
Factory•default:•Disable
٧
Repeat (repeat ON/OFF)
٧
Single (single ON/OFF)
From•start•recording•date•to•end•recording•date,•it•
records•data•at•from•the•set•start•time•to•the•set•end•
time.•
Starts•recording•at•the•start•set•time•on•start•date•and•
nishes•recording•at•the•end•set•time•on•end•date.
Ex)•SV•of•record•zone•division:•None•
Ex)•SV•of•record•zone•division:•5
٧
Two Unit
For•compound•pressure,•if•input•pressure•is•lower•than•
atmospheric•pressure(0),•it•displays•the•degree•of•a•
vacuum•with•mmHg•unit.•If•input•pressure•is•higher•
than•or•same•as•atmospheric•pressure(0),•it•displays•
positive•pressure•with••kg/cm
2
•unit.
When•using•Two•Unit•function,•lower•limit•value•is•xed•
as•-760mmHg•and•kg/cm
2•
value•is•able•to•set•within•set•
range•1•to•35.
Two•Unit•limits•scale•point•as••0•↔•0.0•↔•0.00•.•When•
using•Two•Unit,•display•unit•is•automatically•changed•
as•mmHg•or•kg/cm
2
.
The•calculation•with•Record•Method•(Data•storage•
method)•and•Filter•type•(Input•digital•lter)•is•impossible•
and•ignored•due•to•different•type•of•two•unit•value.
•
•
•Set•range:•1•to•35
•
•
•Factory•default:•-
Ex)•If•pressure•range•is•-760mmHg•to•3kg/cm
2
,•and•
pressure•transmitter•outputs•4-20mA,•for•4mA•
input•it•displays•-760mmHg,•8mA•input•is•unit•
changing•point.•For•20mA•input,•it•displays•3kg/cm
2
.
٧
Open parameter set file [ Load Set File ]
Applies•set•value•of•saved•parameter•set•le.••
When•applying•this•set,•backup•data,•user•unit•and•
booting•logo•are•not•changed.•
None,•Default.pms•le•is•activated•and•if•there•is•
User1.pms•to•User5.pms,•User1.pms(USB)•to•User5.
pms(USB)•le(parameter•set•save•le),•it•is•activated.
•
•
Set•range:•
• None•↔•Default.pms•↔•User1.pms•to•User5.pms•
↔•User1.pms(USB)•to•User5.pms(USB)
•
•
•Factory•default:•None