6 Parameter Settings and Functions     
44    © Copyright Reserved Autonics Co., Ltd. 
6.1.6  SV high/low-limit value 
You can limit the SV (setting value) range within the temperature range of the sensor or analog 
input type (refer to 6.1.1 Input type and temperature range) in order to prevent the system from 
controlling with improper SV. 
 
Setting group  Parameter  Setting range 
Unit 
Initial Setting 
Refer to the below. 
℃/℉  
  SV low-limit value: Min. value of input sensor range to SV high-limit - 1 digit 
  SV high-limit value: SV low-limit + 1 digit to max. value of input sensor range 
 
  Attempts to set the limits outside the min/max input range, or analog's high/low-limits, are 
not accepted. Instead, the previous settings are retained. 
  SV (setting value) can only be set within the SV low-limit and SV high-limit. 
  SV low-limit cannot exceed SV high-limit. 
  Changing the input sensors automatically changes the SV high/low-limit settings to max/min 
values of the changed input sensor input. The user is required to reset related settings.