6 Parameter Settings and Functions 
© Copyright Reserved Autonics Co., Ltd.    81 
6.6  Monitoring function 
6.6.1  Control output MV monitoring 
Monitors and displays the current control output MV. 
6.6.2  Heating MV monitoring 
Displays the current heating MV during heating control or heating and cooling control. Users 
may manually adjust the MV to control the temperature. 
  Measurement range: 0.0 to 100.0% 
6.6.3  Cooling MV monitoring 
Displays the current cooling MV during cooling control or heating and cooling control. Users may 
manually adjust the MV to control the temperature. 
  Measurement range: 0.0 to 100.0% 
6.6.4  Heater current monitoring 
A feature that monitors and displays the current of a heater (load) being controlled by control 
output. 
  Measurement range: 0.0 to 50.0A 
 
The current value of a heater (load) is measured and displayed through the current transformer. 
 
Setting group  Parameter  Setting range 
Unit 
Monitoring  Heating_MV  0.0 to 100.0  -  % 
Monitoring  Cooling_MV  0.0 to 100.0  -  % 
Monitoring  CT1_Heater Current  0.0 to 50.0  -  A 
Monitoring  CT2_Heater Current  0.0 to 50.0  -  A 
Availability of the heater current monitoring function is different by model and control output type.   
Model  Control output type  Heater current monitoring 
TM□-□□R□ (Relay output)  Relay output  ○ 
TM4□-□□S□   
(SSR drive output) 
ON/OFF control    ○ 
Cycle control    X 
Phase control    X 
TM2□-□□C□   
(Current or SSR drive output) 
Current output  X 
SSR drive output  ○