6 Parameter Settings and Functions 
© Copyright Reserved Autonics Co., Ltd.    57 
6.3.3  PID control 
PID control is a combination of proportional (P), integral (I), and derivative (D) controls and offers 
superb control over control subjects, even with a delay time. 
Proportional control (P) implements smooth, hunting-free control; integral control (I) 
automatically corrects offsets; and derivative control (D) speeds up the response to disturbance. 
Through these actions, PID control realizes ideal temperature control. 
 
 
How to apply PID control 
  Proportional (P) control: Set both integral and derivative times to 0 after PID control is 
selected. 
  Proportional-Integral (PI) control: Set the derivative time to 0 after PID control is selected. 
  Proportional-Derivative (PD) control: Set the integral time to 0 after PID control is selected. 
  When using the multi-SV function, the same PID time constant will be applied to SV0 to 
SV3. 
6.3.3.1  Proportional band   
When PV (present value) is within the proportional band (P), the ON/OFF ratio needs to be 
adjusted during the proportional period (T). The defined proportional control (time proportional 
control) section is referred to as the proportional band. 
Parameter 
Unit 
Control 
Operation 
Heating, PID  Heating_Proportional Band 
0.1 to 
999.9 
10.0 
℃/℉ 
Cooling, PID  Cooling_Proportional Band 
6.3.3.2  Integral time   
MVs from integral and proportional operation become the same when deviation is consistent. 
The time taken for the two MVs to match is called the integral time. 
Setting group 
Parameter 
Unit 
Control 
Operation 
Heating, PID  Heating_Integral Time 
0 to 9999  0  Sec. 
Cooling, PID  Cooling_Integral Time 
 
  Integral control is not conducted if the integral time is set to 0. 
  Setting the integral time too short can intensify Correction Movements and cause hunting.