Planning
Technical Handbook, AutroGuard Multicriteria Protector Series V-430, V-530, V-100, V110 and V-120,
AutroGuard-Technical-Handbook, Doc-1004339, Revision 1, 2020-06-29,
Autronica Fire and Security
Page 44
8.4 Current Consumption on Detection Loop
The current consumption for the base and the protector head must
be taken into consideration during planning.
In addition, the following must be taken into consideration:
the loop driver’s maximum current limitation (refer to datasheets
for loop drivers)
the total current consumption on the detection loop
add-on features as VAD and sounders
number of active alarm indicators
The table below shows the average current consumption for different
units and different states.
Unit
State
Current Consumption
(average)
Base
Idle
60µA
Protector head
Idle
60µA
Base + protector head
Idle
120µA
Base + protector head
Alarm (Red LED indicator ON)
2,1mA
Base + protector head
Fault (Yellow LED indicator ON)
2,8mA