Loading...
Instructions, AutroFlame X33AF, 116-P-X33AF/IGB, rev. E, 2013-08-13, P/N 95-8625-17.1, Rev: 2/13
Autronica Fire and Security AS
Page A-3
FM Approval and Performance Report – Continued
RESPONSE CHARACTERISTICS IN THE PRESENCE OF FALSE ALARM SOURCES
Very High Sensitivity
False Alarm Source
Distance
feet (m)
Fire Source
Distance
feet (m)
Average Response Time
(seconds)
Sunlight, direct, modulated, reected 6-inch propane 6 (1.8) < 10
Vibration
N/A
3-inch propane 10.5 (3.2) < 10
Radio frequency interference 1 (0.3) 3-inch propane 12 (3.7) < 10
Arc welding, #7014 40 (12.2) 1 x 1 foot n-Heptane 40 (12.2)
4
6 kw heater, modulated 80 (24.4) 1 x 1 foot n-Heptane 80 (24.4)
2
6 kw heater, unmodulated 10 (3) 1 x 1 foot n-Heptane 80 (24.4)
3
250 w vapor lamp, modulated 3 (0.9) 1 x 1 foot n-Heptane 80 (24.4)
2
300 w incandescent lamp, modulated 3 (0.9) 1 x 1 foot n-Heptane 80 (24.4)
7
500 w shielded quartz halogen lamp, modulated 8 (2.4) 1 x 1 foot n-Heptane 80 (24.4)
2
500 w unshielded quartz halogen lamp, modulated 8 (2.4) 1 x 1 foot n-Heptane 80 (24.4)
3
1500 w electric radiant heater, modulated 10 (3) 1 x 1 foot n-Heptane 80 (24.4)
5
Two 34 w uorescent lamps, modulated 3 (0.9) 1 x 1 foot n-Heptane 80 (24.4)
3
Medium Sensitivity
False Alarm Source
Distance
feet (m)
Fire Source
Distance
feet (m)
Average Response Time
(seconds)
Sunlight, direct, modulated, reected 6-inch propane 6 (1.8) < 4
Vibration* N/A N/A N/A N/A
Radio frequency interference 1 (0.3) 6-inch propane 6 (1.8) < 1
Arc welding, #7014 10 (3) 1 x 1 foot n-Heptane 40 (12.2)
4
6 kw heater, modulated 60 (18.3) 1 x 1 foot n-Heptane 60 (18.3)
2
6 kw heater, unmodulated 10 (3) 1 x 1 foot n-Heptane 60 (18.3)
2
250 w vapor lamp, modulated 3 (0.9) 1 x 1 foot n-Heptane 60 (18.3)
1
300 w incandescent lamp, modulated 3 (0.9) 1 x 1 foot n-Heptane 60 (18.3)
1
500 w shielded quartz halogen lamp, modulated 8 (2.4) 1 x 1 foot n-Heptane 60 (18.3)
1
500 w unshielded quartz halogen lamp, modulated 8 (2.4) 1 x 1 foot n-Heptane 60 (18.3)
1
1500 w electric radiant heater, modulated 10 (3) 1 x 1 foot n-Heptane 60 (18.3)
6
Two 34 w uorescent lamps, modulated 3 (0.9) 1 x 1 foot n-Heptane 60 (18.3)
2
* Fire was veried with very high sensitivity only.