Instructions, AutroFlame X33AF, 116-P-X33AF/IGB, rev. E, 2013-08-13, P/N 95-8625-17.1, Rev: 2/13
Autronica Fire and Security AS
Page A-5
FM Approval and Performance Report – Continued
FALSE ALARM IMMUNITY
Very High Sensitivity
False Alarm Source
Distance
feet (m)
Modulated Response Unmodulated Response
Sunlight, direct, reected — No alarm No alarm
Vibration N/A No alarm N/A
Radio frequency interference 1 (0.3) No alarm (keyed) No alarm (steady)
Arc welding 40 (12.2) No alarm No alarm
6 kw heater 3 (0.9) No alarm No alarm
250 w vapor lamp 3 (0.9) No alarm No alarm
300 w incandescent lamp 3 (0.9) No alarm No alarm
500 w unshielded quartz halogen lamp 8 (2.4) No alarm No alarm
500 w shielded quartz halogen lamp 8 (2.4) No alarm No alarm
1500 w electric radiant heater 3 (0.9) No alarm No alarm
Two 34 w uorescent lamps 3 (0.9) No alarm No alarm
Medium Sensitivity
False Alarm Source
Distance
feet (m)
Modulated Response Unmodulated Response
Sunlight, direct, reected — No alarm No alarm
Vibration N/A No alarm N/A
Radio frequency interference 1 (0.3) No alarm (keyed) No alarm (steady)
Arc welding 10 (3) No alarm No alarm
6 kw heater 3 (0.9) No alarm No alarm
250 w vapor lamp 3 (0.9) No alarm No alarm
300 w incandescent lamp 3 (0.9) No alarm No alarm
500 w unshielded quartz halogen lamp 8 (2.4) No alarm No alarm
500 w shielded quartz halogen lamp 3 (0.9) No alarm No alarm
1500 w electric radiant heater 3 (0.9) No alarm No alarm
Two 34 w uorescent lamps 3 (0.9) No alarm No alarm
T-Low Sensitivity
False Alarm Source
Distance
feet (m)
Modulated Response Unmodulated Response
Sunlight, direct, reected — No alarm No alarm
Vibration — No alarm No alarm
Arc welding 5 (1.5) No alarm No alarm
6 kw heater 3 (0.9) No alarm No alarm
70 w sodium vapor 3 (0.9) No alarm No alarm
250 w vapor lamp 3 (0.9) No alarm No alarm
300 w incandescent lamp 3 (0.9) No alarm No alarm
500 w shielded quartz halogen lamp 3 (0.9) No alarm No alarm
1500 w electric radiant heater 3 (0.9) No alarm No alarm
Two 34 w uorescent lamps 3 (0.9) No alarm No alarm
Low Sensitivity
False Alarm Source
Distance
feet (m)
Modulated Response Unmodulated Response
Sunlight, direct, reected — No alarm No alarm
Vibration — No alarm No alarm
Radio frequency interference N/A No alarm N/A
Arc welding 5 (1.5) No alarm No alarm
6 kw heater 3 (0.9) No alarm No alarm
250 w vapor lamp 3 (0.9) No alarm No alarm
300 w incandescent lamp 3 (0.9) No alarm No alarm
500 w shielded quartz halogen lamp 3 (0.9) No alarm No alarm
1500 w electric radiant heater 3 (0.9) No alarm No alarm