Appendix
Operator's Handbook, AutroSafe Interactive Fire Alarm System, Release 3, ASAFE-FO/FE Rev. E, 021105,
Autronica Fire and Security AS
Page 124
15.3 Action Digits Table - Operation Mode
All action digits that may appear in Operation Mode are listed in the
table below.
Action Digits
Action Digit When action is available Used to…..
ACCEPT FIRE
WARNING
4
JKL
Available when the selected event is
a non-accepted Fire Warning.
accept the selected Fire
Warning.
ACCEPT FAULT
WARNING
3
GHI
Available in the Info window when the
selected event is a non-accepted
Fault Warning.
accept the selected Fault
Warning.
RESOUND
1
ABC
Available in the event of a fire alarm
when alarms have been silenced.
resound all Fire Alarm
Devices (FAD) related to the
alarms within the operation
zone of the operator panel.
REACTIVATE
3
GHI
Available when there exists alarm
disabled points
reactivate (enable) the alarm
disabled points.
ACTIVATE
2
DEF
Available when one or several
Delayed Action detection zones have
entered a fire alarm state and are in
their T1 and T2 periods.
(Not included in SOLAS version).
immediately activate the
delayed actions of all active
Delayed Action detection
zones.
SHOW POINTS
1
ABC
Available when the selected event is
a Detection Zone.
show point information.
SHOW SUPPR.
INFO
4
JKL
Available when conditions are active,
but suppressed.
show suppressed information
if other conditions are active,
but suppressed.
SHOW FIRE
INFO
1
ABC
Available during a fire alarm condition
when Show Suppressed Information
has been pressed.
show suppressed fire
information
SHOW FIRE
WARNING
1
ABC
Available during a fire alarm condition
when Show Suppressed Information
has been pressed and there exists
fire warnings.
show suppressed fire
warnings
SHOW FAULT
WARNING
2
DEF
Available during a fire alarm condition
when Show Suppressed Information
has been pressed and there exists
fault warnings.
show suppressed fault
warnings
SHOW
DISABLEMENTS
3
GHI
Available during a fire alarm condition
when Show Suppressed Information
has been pressed and there exists
disablements.
show suppressed
disablements
SHOW TESTS
4
JKL
Available during a fire alarm condition
when Show Suppressed Information
has been pressed and there exists
tests.
show suppressed tests
ENABLE
3
GHI
Available when the selected event is
a disablement.
enable the disablement.