EasyManua.ls Logo

AUX AMWM-H09/4R3 - Long Piping Length

AUX AMWM-H09/4R3
200 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
AUX DC Inverter Free Match 50HZ R32
3. Long piping length
Cooling capacity (KBtu/h)
14K
18K
21K
27K
36K
42K
Connection
Pipe(mm)
Liquid pipe
Φ6.35*2
Φ9.52*3
Φ9.52*4
Φ9.52*5
Gas pipe
Φ9.52*2
Φ15.88*3
Φ15.88*4
Φ15.88*5
Max. length for all rooms (m)
40
60
80
Max. length for one IU (m)
25
30
35
Max. height difference
between IU and OU (m)
15
Max. height difference
between IUs (m)
10
Caution:
1. The standard Pipe length is 5m, if the pipe length is less than this then no additional
charging is necessary. If the pipe length is more than this then you should charge more refrigerant
into the system according to the above Charging Data
2. The thickness of the pipe is 0.6-1.0, bearing pressure is 4.2MPa;
3. If the connection pipe is too long, the cooling capacity and stability would be decreased.
And the more bend quantity, the resistance in the piping system would be bigger, then the cooling
and heating capacity would be decreased even lead to compressor broken. We suggest you to
use the shortest connection pipe according to the pipe length parameter in this manual. If the
height difference between outdoor and indoor unit is more than 5m, an oil trap should be installed
in the gas pipe for every 10 meters.

Table of Contents

Related product manuals