3.3.2 - PRE-FLASHING TIME
The flashing light is an important safety
component. It starts when a command to set the
gate in motion is received by the electronic card.
The gate is set in motion around one second after a
command is received.
In certain use cases, it is better that the time between
receiving a motion command and the start of the
manoeuvre is longer. It is possible to increase this
time to 3 seconds.
To set the pre-flashing time, follow the
procedure below
Press PROG” for 3 seconds. L0 will flash once
and L1 will switch on.
• Press “PROG” for 3 seconds. L0 will flash twice.
Press PROG for 3 seconds. L0 will flash 3 times.
Press “+” once. L2 will turn on instead of L1.
• Press OK.
If L1 is off, the time is 1 second. Press “+” to
increase it to 3 seconds, then OK to confirm. All
LEDs will turn on and off to confirm the operation.
If L1 is on, the time is 3 seconds. Press “” to
reduce it to 1 second, then OK to confirm. All
LEDs will turn on and off to confirm the operation.
D - BEGINNING OPERATION