14 AVTECH Software Inc.
Conguration And Setup Screens Room Alert 26W
SNMP Queries (SNMP Get)
SNMP Queries or Get requests are performed by a SNMP enabled software application to retrieve
specic information from an SNMP compliant device on the network. The query or request will be sent
to the IP address of the Room Alert 26W unit using a SNMP community name on UDP port 161. The
SNMP community name in use for that device or network must match the name in the ‘SNMP Read
Community Name’ eld on the ‘SNMP’ tab of the ‘Settings’ screen. If use of a third party application
is desired, the SNMP protocol used must be version 1 and the MIB les for the Room Alert 26W unit
must be loaded properly in the software application in order to retrieve the SNMP MIB Objects that will
return sensor data from the Room Alert 26W unit to the monitoring software.
SNMP Traps
SNMP Traps are sent from an SNMP compliant device on the network and received by a SNMP enabled
software application capable of receiving SNMP Traps. To congure the Room Alert 26W unit to send
SNMP Traps to a specic IP address, enter the IP address in one of the three ‘SNMP Trap Recipient’
elds on the ‘SNMP’ tab. SNMP Traps sent from the Room Alert 26W unit are sent using an SNMP
community name of ‘public’. If use of a third party application is desired, be sure to load the Room Alert
26W MIB le or the information received in the SNMP Trap will not be translated.
Monitoring With PageR Enterprise (PageR)
PageR is a network-wide monitoring application included (bundled) with the purchase of a Room