6
Chapter 3.   Communication Settings
For communications with this device, the following settings must be configured.
1. Device address
2. Transmission speed
3. Data format
Each setting is explained below.
Each setting can be configured either in the setting mode of this device or with the Smart Loader Package.
 Note
•  For details about each setting, refer to  Installation and Usage Guide for Smart 
Loader Package Model SLP-A55 for Burner Controller Model AUR_55, Document 
No. CP-UM-5956JE. 
  Handling Precautions
•  After setting the device address, transmission speed, and data format, it is 
necessary to briefly turn off the power to this device and then turn it back on 
again.  
When the power is turned on, the new device address, transmission speed, 
and data format settings will take effect.
Device address
The setting range is from 1 to 32.
Make sure that there are no duplicate device addresses on the same transmission 
line.
The default setting is 1.
Transmission speed
The speed can be selected from 4800, 9600, and 19200 bps.
The preset speed is 19200 bps.
Data format
The format can be selected from:  
  8 bits, even parity, 1 stop bit  
  8 bits, even parity, 2 stop bits 
  8 bits, odd parity, 1 stop bit 
  8 bits, odd parity, 2 stop bits
The preset format is 8 bits, even parity, 1 stop bit.