25
Chapter 5.  Communication Data
Communication data table
Access to read/write data
  No symbol  : Accessible
  x  : Not accessible
CPL communication RS/WS commands
  Put “W” after the decimal data address.
CPL communication RD/WD/RU/WU commands
  Use hexadecimal data addresses.
  Handling Precautions
•  Do not access addresses that are not listed.  
Operation is not guaranteed if an address that is not listed is accessed.
Data type Data name Address Access Description Note
Decimal
(W)
Hex
(H)
Read Write
Maintenance 
data
Model setup 3000 0BB8 x Bits 0 to 7
Undefined
Bits 8 to 11: flame sensor
1: undefined
2: AUD300
3: flame rod
4: undefined
Bits 12 to 15
Undefined
Version 3001 0BB9 x
Check SUM  3003 0BBB x
Check SUM  3004 0BBC x
Product serial number 3005 0BBD x
Date code 3006 0BBE x
Start signal / reset switch 3016 0BC8 x Bit 0: contact reset input
0: open
1: short circuit
Bit 1: startup input
0: open
1: short circuit
Bit 2: DISP switch
0: not pushed
1: pushed
Bit 3: reset switch
0: not pushed
1: pushed
Bits 4 to 15
Undefined
Flame signal 3019 0BCB x Bit 0: flame
0: no
1: yes
Bits 1 to 15
Undefined
Event output 3020 0BCC x Bit 0: event output
0: OFF
1: ON
Bits 1 to 15
Undefined
Relay output 3022 0BCE x Bits 0 to 3
Undefined
Bit 4: start check relay
0: OFF
1: ON
Bit 5: flame relay
0: OFF
1: ON
Bits 6 to 12
Undefined
Bit 13: event relay
0: OFF
1: ON
Bit 14: K7
0: OFF
1: ON
Bit 15: K8
0: OFF
1: ON
Bits 0–7, 12–15 undened
(bits)
15 12 11 8 7 4 3 0
: 1 (bit ON)
: 0 (bit OFF)
How to read the table
Flame 
sensor
2: AUD300
3: ame rod