38
Chapter 6. Details of Functions via Communication
To use events
To use the event function, set up using host communication or Smart Loader
Package model SLP-A55.
Writing 2-word event settings
When writing a setting for a 2-word event, write the two words consecutively.
Be sure to observe the order of the addresses.
Writing data in the wrong order results in an error. In this case, the setting is not
written.
The following is a list of 2-word event items.
Item name Address Description Sample write command
Condition for event 7100 1BBC Bit 0: UV flame detector check
(combustion time)
0: not set
1: set
Bit 1: product service life check (total
operating time)
0: not set
1: set
Bit 2: product service life check (total
combustion count)
0: not set
1: set
Bit 3: false flame
0: not set
1: set
Bit 4: flame relay OFF
0: not set
1: set
Bit 5: flame relay OFF (shutter closed)
0: not set
1: set
Bits 6 to 15
Undefined
“UV flame detector check (combustion
time) A1” event
Fixed length continuous data write
command (WD command):
WD1BBC000100351
or
WD1BBC0001
WD1BBD0035
Continuous data write command (WS
command):
WS,7100W,1,53
or
WS,7100W,1
WS,7101W,53
7101 1BBD 0035H
UV flame detector
check (combustion
time)
7109 1BC5 0 to 61A8H (0 to 25000 hours)
To set a value of 25000 hours
Fixed length continuous data write
command (WD command):
WD1BC561A80036
or
WD1C5C61A8
WD1C6D0036
Continuous data write command (WS
command):
WS,7109W,25000,54
or
WS,7109W,25000
WS,7110W,54
7110 1BC6 0036H

Table of Contents