43
Chapter 6. Details of Functions via Communication
To initialize each type of data record, write the value shown in the following table using the WD or WU command.
For example, writing “005AH” to 3552W clears each alarm count to zero.
Item name Address Description Write data
Alarm count clear 3552W Integrated Value: Internal error (flame circuit) to host
communication setting data
(3350W to 3367W)
005AH
Alarm monitor clear 3553W Alarm History-1 to -16
(5000 to 5095W)
005AH
Reset all event counts
to 0
3557W Event A1 count (3393W) CA51H
Event A2 count (3394W) CA52H
Event A3 count (3395W) CA53H
Event A4 count (3396W) CA54H
Event A5 count (3397W) CA55H
Event A6 count (3398W) CA56H
Initialize all CAFFH
Initialization of
operating time /
combustion time /
combustion count
3558W Operating time (3387 to 3388W) CA51H
Combustion time (3389 to 3390W) CA52H
Combustion count (3391 to 3392W) CA53H
Initialize all CAFFH
6 - 3 Data Initialization