Chapter 6. Details of Functions via Communication
This function supports maintenance for the playback monitor, etc.
You can read maintenance information (data every 0.1 second) for 10 seconds after a trigger occurs.
Trigger
The trigger occurs when flame monitoring (PF) starts.
Recorded information
Item Address Bit position Data information
- 8100*
2
0
Start input 1 0=OFF/1=ON
- 2
- 3
Flame 4 0=OFF/1=ON
- 5
Start check relay 6 0=OFF/1=ON
Flame relay 7 0=OFF/1=ON
- 8
Shutter*
1
9 0=OFF/1=ON
- 10
Flame level*
1
11 to 13 [0 to 5]
- 14
- 15
Operating status No. 8101*
2
0 to 7
Operating status No.
table (p.36)
Flame voltage 8 to 15 0 to 50 [0.1 V]
*1. AUR355C only. Undefined for AUR355B.
*2. Addresses 8102 to 8299 have the same information.
To read recorded information
The following is the procedure for reading playback monitor data after a trigger
occurs.
Data name Address Description
Flame logger processing
status
8000 5AH : processing under way
Other than 5AH : normal
(1) Check that the flame logger processing status (8000) is not “Processing under
w a y.”
(2) Read the recorded information (8100 to 8299).
6 - 5 Flame Logger