27
Chapter 5. Communication Data
Data type Data name Address Access Description Note
Decimal
(W)
Hex
(H)
Read Write
Maintenance
data
Event flag 3044 0BE4 x Bit 0: UV flame detector check
(combustion time)
0: no
1: yes
Bit 1: product service life check (total
operating time)
0: no
1: yes
Bit 2: product service life check (total
combustion count)
0: no
1: yes
Bit 3: false flame
0: no
1: yes
Bit 4: flame relay OFF
0: no
1: yes
Bit 5: flame relay OFF (shutter closed)
0: no
1: yes
Bits 6 to 15
Undefined
Present event occurrence
status
Power frequency flag 3045 0BE5 x Bit 0: power frequency flag
0: 50 Hz
1: 60 Hz
Flame level (shutter open) (0 to 100 %) 3046 0BE6 x 0 to 100 % The number of times the
flame level (shutter open)
is maintained for 1 second
is converted to a number
from 0 to 100.
Flame level (shutter closed) (0 to 100 %) 3047 0BE7 x 0 to 100 % The number of times the
flame level (shutter closed)
is maintained for 1 second
is converted to a number
from 0 to 100.
Flame level (100 ms) 3048 0BE8 x 0 to 5 times The number of times the
flame level is reached for
100 ms
Model Type 3101 0C1D x 3C3CH
Flame sensor 3105 0C21 x CC33H: AUD300
9966H: flame rod
Flame failure response time 3123 0C33 x BF40H = 2 seconds max.
7F80H = 4 seconds max.
Host communication: Address (RS-485) 3182 0C6E x 08XXH = XX, device address (1 to 32) in
hex notation
Change this setting using
Smart Loader Package
model SLP-A55.
Host communication: Baud rate (RS-485) 3183 0C6F x 0900H = 4800 bps
0940H = 9600 bps
0980H = 19200 bps
Change this setting using
Smart Loader Package
model SLP-A55.
Host communication: Data format (RS-
485)
3184 0C70 x 0A00H = Even parity, 1 stop bit
0A33H = Even parity, 2 stop bits
0A66H = Odd parity, 1 stop bit
0A99H = Odd parity, 2 stop bits
Change this setting using
Smart Loader Package
model SLP-A55.
Apparatus information 1 3189 0C75 x 0000H to FFFFH Model information (ASCII
character string that
indicates the model)
Apparatus information 2 3190 0C76 x 0000H to FFFFH
Apparatus information 3 3191 0C77 x 0000H to FFFFH
Apparatus information 4 3192 0C78 x 0000H to FFFFH
Apparatus information 5 3193 0C79 x 0000H to FFFFH
Apparatus information 6 3194 0C7A x 0000H to FFFFH
Apparatus information 7 3195 0C7B x 0000H to FFFFH
Apparatus information 8 3196 0C7C x 0000H to FFFFH
Apparatus information 9 3197 0C7D x 0000H to FFFFH
Apparatus information 10 3198 0C7E x 0000H to FFFFH