30
Chapter 5. Communication Data
Data type Data name Address Access Description Note
Decimal
(W)
Hex
(H)
Read Write
Initialization Alarm count clear 3552 0DE0 Write: clear request = 5AH,
Read: clear complete = 00H
Clears the cumulative
values of all alarms to zero
at once.
Alarm monitor clear 3553 0DE1 Write: clear request = 5AH,
Read: clear complete = 00H
Clears all alarm records at
once.
Event clear 3555 0DE3 Write Clears A1 : CA51H
Clears A2 : CA52H
Clears A3 : CA53H
Clears A4 : CA54H
Clears A5 : CA55H
Clears A6 : CA56H
Clears A1 to A6
: CAFFH
Events can be individually
cleared.
You can also clear all events
at the same time.
Read Clear operation completed
: 3CH
Reset all event counts to 0 3557 0DE5 Write Clears A1 : CA51H
Clears A2 : CA52H
Clears A3 : CA53H
Clears A4 : CA54H
Clears A5 : CA55H
Clears A6 : CA56H
Clears A1 to A6
: CAFFH
Event counts can be
individually reset to zero.
You can also reset all event
counts to zero at the same
time.
Read Clear operation completed
: 3CH
Initialization of operating time /
combustion time / combustion count
3558 0DE6 Write Clears the operating time
: CA51H
Clears the combustion time
: CA52H
Clears the combustion
count : CA53H
Clears all : CAFFH
Data can be individually
reset to zero.
You can also reset all data
records to zero at the same
time.
Read Initialization complete
: 3CH
Data type Data name Address Access Description Note
Decimal
(W)
Hex
(H)
Read Write
Playback
monitor
Event code & operating status No. when
an event occurs
4000 0FA0 x
Playback monitor recorded
information (p.44)
Index 4001 0FA1 x
Playback monitor recorded
information (p.44)
Recorded data 8.0 s before event 4002 0FA2 x
Playback monitor recorded
information (p.44)
Recorded data 8.0 s before event 4003 0FA3 x
Playback monitor recorded
information (p.44)
x
Recorded data 1.9 s after event 4200 1068 x
Playback monitor recorded
information (p.44)
Recorded data 1.9 s after event 4201 1069 x
Playback monitor recorded
information (p.44)
Playback monitor data processing status 4202 106A x Processing under way = 5AH, Normal
≠ 5AH
Integrated Value:Play-back (High) 4205 106D x 0 to FFFFFFFFH (times) The number of times
playback data was saved in
nonvolatile memory.
Record is kept for up to
100,000 times.
The count continues to be
incremented after 100,000
times but it is not saved in
nonvolatile memory.
As a result, the count
returns to 100,000 when the
power is turned on.
(Low) 4206 106E x

Table of Contents