Chapter 6. Details of Functions via Communication
z
False flame (A4)
This event occurs if the flame relay is on before startup and the start check relay
does not turn on after startup.
Write address* Note
7101W (bit 3) Factory setting: 0
*Use address 7061W (bit 3) when reading data.
z
Flame relay OFF (A5)
This event occurs if startup input is on during flame monitoring (PF) and the flame
relay is turned OFF (flame failure).
Write address* Note
7101W (bit 4) Factory setting: 0
*Use address 7061W (bit 4) when reading data.
z
Flame relay OFF (shutter closed) (A6)
AUR355C: This event occurs if startup input is on and the shutter remains closed
for about 5 seconds.
AUR355B: This event does not occur.
Write address* Note
7101W (bit 5) Factory setting: 0
*Use address 7061W (bit 5) when reading data.