12-2
Symptom Cause and Remedy
Even when valve plug
is in closed position,
large flow leaks to
downstream side.
Air leak at actuator section.
For trial, apply the air supply pressure or atmospheric
pressure to the actuator. (Check the air supply source and
positioner.)
Check whether the valve plug is actually the closed position
or not. (Check the valve plug lift)
Check the plug seat ring for corrosion and erosion.
Check the guide sections for binding.