3-11
Chapter 3. SP/EV BANK SETTINGS
Loop 2 recipe bank (L2.rec)
Display
Loop number
and SP group
(
auxiliary display
)
Item Settings and descriptions Initial
value
User
setting
Remarks
SP 2.0 1.
LSP SP low limit to SP high limit 0 The decimal point position is
determined by the decimal point
position for the loop PV/SP.
E09 2.0 1.
Event 9 main setting -19999 to +32000 U 0 The decimal point position is
determined by the decimal
point position for the event
configuration.
E09.SB 2.0 1.
Event 9 sub setting
E 10 2.0 1.
Event 10 main setting
E 10.SB 2.0 1.
Event 10 sub setting
E 1 1 2.0 1.
Event 11 main setting
E 1 1.SB 2.0 1.
Event 11 sub setting
E 12 2.0 1.
Event 12 main setting
E 12.SB 2.0 1.
Event 12 sub setting
E 13 2.0 1.
Event 13 main setting
E 13.SB 2.0 1.
Event 13 sub setting
E 14 2.0 1.
Event 14 main setting
E 14.SB 2.0 1.
Event 14 sub setting
E 15 2.0 1.
Event 15 main setting
E 15.SB 2.0 1.
Event 15 sub setting
E 16 2.0 1.
Event 16 main setting
E 16.SB 2.0 1.
Event 16 sub setting
P 2.0 1.
Proportional band 0.1 to 3200.0 % 5.0
I 2.0 1.
Integral time 0 to 32000 s, 0.0 to 3200.0 s or 0.00 to
320.00 s (no integral control action
when set at 0, 0.0 or 0.00)
120 The decimal point position is
determined by the decimal
point position for the control
parameter.
D 2.0 1.
Derivative time 0 to 32000 s, 0.0 to 3200.0 s or 0.00 to
320.00 s (no derivative control action
when set at 0, 0.0 or 0.00)
30
OL 2.0 1.
Output low limit -10.0 to +110.0 % 0.0
OH 2.0 1.
Output high limit 100.0
RE 2.0 1.
Manual reset 50.0
P-C 2.0 1.
Proportional band for cool side 0.1 to 3200.0 % 5.0
I -C 2.0 1.
Integral time for cool side 0 to 32000 s, 0.0 to 3200.0 s or 0.00 to
320.00 s (no integral control action
when set at 0, 0.0 or 0.00)
120 The decimal point position is
determined by the decimal
point position for the control
parameter.
D-C 2.0 1.
Derivative time for cool side 0 to 32000 s, 0.0 to 3200.0 s or 0.00 to
320.00 s (no derivative control action
when set at 0, 0.0 or 0.00)
30
OL.C 2.0 1.
Output low limit for cool side -10.0 to +110.0 % 0.0
OH.C 2.0 1.
Output high limit for cool side 100.0
OI 2.0 1.
Initial output of PID control 0.0
SP 2.02.
LSP Same as SP group 1 0 Same as SP group 1
E09 2.02.
Event 9 main setting 0
E09.SB 2.02.
Event 9 sub setting
E 10 2.02.
Event 10 main setting
E 10.SB 2.02.
Event 10 sub setting
E 1 1 2.02.
Event 11 main setting
E 1 1.SB 2.02.
Event 11 sub setting
E 12 2.02.
Event 12 main setting
E 12.SB 2.02.
Event 12 sub setting
E 13 2.02.
Event 13 main setting
E 13.SB 2.02.
Event 13 sub setting
E 14 2.02.
Event 14 main setting
E 14.SB 2.02.
Event 14 sub setting
E 15 2.02.
Event 15 main setting
E 15.SB 2.02.
Event 15 sub setting
E 16 2.02.
Event 16 main setting
E 16.SB 2.02.
Event 16 sub setting
P 2.02.
Proportional band 5.0
I 2.02.
Integral time 120
D 2.02.
Derivative time 30
OL 2.02.
Output low limit 0.0
OH 2.02.
Output high limit 100.0
RE 2.02.
Manual reset 50.0
P-C 2.02.
Proportional band for cool side 5.0
I -C 2.02.
Integral time for cool side 120
D-C 2.02.
Derivative time for cool side 30
OL.C 2.02.
Output low limit for cool side 0.0
OH.C 2.02.
Output high limit for cool side 100.0
OI 2.02.
Initial output of PID control 0.0