PROGRAMMING
MPORTANTI
You must connect terminals 1 and 5 together to enable the programming mode. After all programming is complete, remove the
connection between terminals 1 and 5 to prevent the unit from being reprogrammed by mistake.
To access the programming screens, press repeatedly until the Program Mode (1 through 7) you want displays on
the screen.
1. Once you select a program, press
R
to either cause the left digit of that value to ash (scale factors modes 1, 4 & 6), or
to change the parameters for the other programming modes (Decimal Point Position and Totalizer Reset).
2. On program modes 1, 4 & 6, use
R
and in combination to choose individual digits and change their value.
OTE:N On program modes 1, 4 & 6, you can advance to the next program mode only if a digit is not flashing. Press
R
until the display stops flashing.
R
1.01.000
Mode 1: Totalizer Scaler multiplies the input pulses by this number (programmable from 0.0001 to 99.9999)
and displays the results as the totalizer value.
R
2. oFF
Mode 2: Totalizer Decimal Point sets the decimal point on the totalizer display from no decimal
(OFF) to 0.00000.
R
3. 1.000
Mode 3: Rate Scale Factor Decimal Point sets the decimal in Rate Scale Factor number, from no
decimal to 0.000.
R
4. 9999
Mode 4: Rate Scale Factor multiplies the input pulses by this number, which can be programmed
in conjunction with the Rate Decimal Point for a number from 0.001 to 9999.
R
5. oFF
Mode 5: Rate Decimal Point sets the decimal point on the Rate of Flow display from no decimal
(off) to 0.0000. You can program the display to have a dead zero (----0), for a 5-digit display with the
least significant digit always being 0.
R
6.0.9999
Mode 6: Pulse Output Scale Factor multiplies the input pulses by a number from 0.0001 to 0.9999
and sends them to output terminals 6 & 7.
R
7. on
Mode 7: Front Panel Reset Enable When set to ON, press
R
to reset the totalizer to zero. When
set to OFF, the totalizer can only be reset through the remote reset input
(see Wiring Instructions” on page 7).
R
8. on
Mode 8: Pulse Output Enable When set to ON, the solid-state relay output will pulse to
re-transmit input pulses. If set to OFF, it will not activate. Use the OFF setting to conserve battery
life if not using the output.
User Manual
Page 9 August 2018 REG-UM-00836-EN-12