4-11
Model M-2000 Mag Meter
Inputs/Outputs
Digital Output Output Type
[1: Normally Open]
[2: Normally Open]
[3: Normally Open]
[4: Normally Closed]
S
The Output Type parameter lets you set the output switch to normally open or
normally closed. If normally open is selected, the output switch is open
(no current) when the output is inactive, and closed (current flows) when the
output is active.
If normally closed is selected, the output switch is closed (current flows) when
the output is inactive, and open (no current) when the output is active.
To change the Output Type, follow these steps from the Inputs/Outputs Main
Menu:
1. Select Digital Output 1, 2, 3 or 4 and press [E] to open the Digital Output
menu.
2. From the Digital Output menu, select Output Type,
and press [E] to open the Output Type display.
3. Select Normally Open or Normally Closed.
4. Press [E] to save the new parameter and return to the Digital Output
menu.
Hardware Type
[3: Open Collector]
[4: Open Collector]
S
The hardware type parameter lets you select the type of hardware used to drive
the output signal: either open collector or solid-state relay.
To change the Hardware Type, follow these steps from the Inputs/Outputs
Main Menu:
1. Select Digital Output 3 or 4 and press [E] to open the Digital Output
menu.
2. From the Digital Output menu select Hardware Type, and press [E] to
open the Hardware Type display.
3. Select Open Collector or Relay.
4. Press [E] to save the new parameter and return to the Digital Output
menu.
Full Scale Frequency
[3: 1000 Hz]
S
This parameter establishes the full scale flow output frequency when the flow
rate equals the configured full scale flow.
To change the Full Scale Frequency, follow these steps from the Inputs/Outputs
Main Menu:
1. Select Digital Output 3 and press [E] to open the Digital Output menu.
2. From the Digital Output menu select Full Scale Frequency, and press
[E] to open the Full Scale Frequency display.
3. Set the full scale frequency value to the desired setting.
4. Press [E] to save the new parameter and return to the Digital Output
menu.