EasyManua.ls Logo

Baelz Automatic BA 373-E45 - Operational Malfunction Checklist

Baelz Automatic BA 373-E45
36 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
BA_373-E45_05_DEF_MJ_2119
33 | 36W. Baelz & Sohn GmbH & Co. · Koepffstrasse 5 · 74076 Heilbronn · Germany · www.baelz.de Seite | Page
Motorized Linear Actuator baelz 373-E45
Malfunction Cause Action required
Actuatornotworking
Powerfailure Determinethecauseandcorrectthe
problem.
Defectivefuse(incontrolcabinet) Determinethecauseandcorrectthe
problem,replacethefuse.
Linearactuatorincorrectlyconnected Re-connectasspeciedoncircuit
diagram(insidecover).
Shortcircuitcausedbyhumidity Determinethecause,drythelinear
actuator;ifnecessary,replacecover
sealandscrewsand/ortprotective
cover.
Shortcircuitcausedbyincorrectconnection Connectcorrectly.
Motorwindingdamagecaused,forexample,
byhighvoltageordefectiveelectronics
Determinecause,measurecurrent
data,comparewithnameplateand
specications,dismantlelinear
actuatorandreturnforrepair.
Voltagedropduetoconnectingcablesbeing
toolongand/orhavinginsufcientcross-
section
Measurecurrentdatawithlinear
actuator,recalculateconnecting
cablesandreplaceasnecessary.
Actuatorrunningerratically,
constantlyopeningand
closing
Poweructuationsexceedpermissible
tolerance
Improvepowersupplyconditions.
Loosecontactinsupplyline Checkandtightenconnections
(terminalblocks).
Actuatorstopsintermittently
Valvejamming Enablesmoothvalvemovement.
Actuatordoesnotmoveto
endposition.Valvefailsto
open/close
Systempressuretoohigh Adjustsystempressure.
Poorinputsignal
-interferingsignals
-signaluctuation
Checkinputsignalatlinearactuator,
correcttheproblemcausingthe
malfunction.
Linearactuatorfailstomove
ordoesnotmovecorrectly
tothepositiondenedby
theinputsignal.
Circuitboarddefective Replacecircuitboard,ifnecessary
dismantleactuatorandreturnfor
repair.
12.1 Checklist for operational malfunctions

Table of Contents