Balluff Network Interface EtherNet/IP
www.balluff.com
10
5 Process Data
5.1. Data
Configuration
BNI EIP-302-105-
Z015
Please enter the following values to your Control System. They describe the datasizes for
input, output and config data.
Instance ID
Data length
INPUT
100
8
OUTPUT
101
6
5.2. Process Data
Inputs
BNI EIP-302-105-
Z015
There are 8 bytes of Input data. Have a look at the tables below to see the mapping of the
process data inputs.
Byte
Bit
Description
7
6
5
4
3
2
1
0
0
I32
I34
I22
I24
I12
I14
I02
I04
Input data
I04
Input on port 0 pin 4
1
I72
I74
I62
I64
I52
I54
I42
I44
2
S3
S2
S1
S0
Short circuit status
Short circuit between Pin 1 and 3
on stated port
3
S7
S6
S5
S4
4
O22
O34
O22
O24
O12
O14
O02
O04
Overload status
O04
Overload on port 0 pin 4
Only if port is configured as output
5
O72
O74
O62
O64
O52
O54
O42
O44
6
0
0
0
0
0
0
PS
PA
Power status
PS: Sensor power
PA: actor power
7
0
0
0
0
0
0
0
0
Reserved
5.3. Process Data
Output
BNI EIP-302-105-
Z015
There are 6 bytes of output data. Have a look at the tables below to see the mapping of the
process data outputs.
Byte
Bit
Description
7
6
5
4
3
2
1
0
0
O32
O34
O22
O24
O12
O14
O02
O04
Output data
O04
Output on port 0 pin 4
1
O72
O74
O62
O64
O52
O54
O42
O44
2
R32
R34
R22
R24
R12
R14
R02
R04
Restart
Restart output here after a
detected short-circuit
3
R72
R74
R62
R64
R52
R54
R42
R44
4
0
0
0
0
0
0
0
0
Reserved
5
0
0
0
0
0
DL
GO
RO
Display Control
DL: Display lock / PLC lock
GO: Green LED on Display on
RO: Red LED on Display on