EasyManuals Logo

Banner DF-G1-NS-2M Install Sheet

Banner DF-G1-NS-2M
10 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #7 background imageLoading...
Page #7 background image
For Sales and Support, Contact Walker EMD • Toll-free: (800) 876-4444 • Tel: (203) 426-7700 • Fax: (203) 426-7800 • www.walkeremd.com
Light SET
Sets a threshold a programmable % offset below the presented condition
Changes output state on any condition darker than the threshold condition
Threshold can be adjusted using “+” and “-” rocker button (Manual Adjust)
Recommended for applications where only one condition is known, for example a stable light background with varying darker targets
See Program Mode on page 3 for programming the Offset Percent setting
A single sensing condition is presented, and the sensor positions a threshold a programmable % offset below the presented condition. When a condition darker than the
threshold is sensed, the output either turns ON or OFF, depending on the LO/DO switch setting (see LO/DO Switch in Top Panel Interface on page 2).
Light SET and Manual Adjust
Moves switching threshold value up or down to make adjustments
Slide Mode switch to ADJ to enter Adjust mode
Press “+” to increase; press “-” to decrease
GREEN display shows the switching threshold value
2 seconds after adjustment, the GREEN display will flash 3 times to confirm
Slide Mode switch to RUN to complete operation
Remember: Manual adjustments are disabled
when Auto Thresholds are ON
Threshold position
adjusted by
Manual Adjust
Sensor positions
threshold a programmable
% offset below the
presented condition
Darkest
(no signal)
Most Light
(saturated
signal)
Output OFF Output ON
Condition
Presented
Figure 5. Light SET (Light Operate shown)
SET Button
0.04 seconds < "Click" < 0.8 seconds
Remote Input
0.04 seconds < T < 0.8 seconds
Result
Note: TEACH Selection must be programmed to Lt SEt (see Program Mode on page 3 )
Enter Adjust
Mode
Set Mode switch to ADJ
No action is required; sensor is ready
for Light SET method
Display: Red - Signal Level; Green -
Threshold
SET Sensing
Condition
Present sensing condition
Click the SET rocker button
Present sensing condition
Single-pulse the remote input
T
Threshold Condition Accepted
Displays read "Lt SEt" then alternate
"PASS" with % Offset*; Sensor returns
to Adjust mode
Threshold Condition Unacceptable
Displays read "Lt SEt" then alternate
FAIL with minimum % Offset* for sens-
ing condition; Sensor returns to Adjust
mode
Return to RUN
Mode
Move Mode switch to RUN
No action required; sensor returns to
RUN mode automatically
Display: Red - Signal Level; Green -
Threshold
* Troubleshooting on page 10 for more explanation of the % Offset displayed after the Light SET method
DF-G1 - Expert Fiber Amplifier Install Sheet
P/N 161275 Rev. A www.bannerengineering.com - tel: 763-544-3164 7

Other manuals for Banner DF-G1-NS-2M

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Banner DF-G1-NS-2M and is the answer not in the manual?

Banner DF-G1-NS-2M Specifications

Power IconPower
supply voltage10 to 30 V dc
power consumption (standard display mode)960 mW
current consumption (standard display mode)< 40 mA at 24 V dc
power consumption (ECO display mode)720 mW
current consumption (ECO display mode)< 30 mA at 24 V dc
Output IconOutput
output configuration1 current sinking (NPN) or 1 current sourcing (PNP) output
output rating100 mA max. load
off-state leakage current (NPN/PNP models)< 5 μA at 30 V dc
on-state saturation voltage (NPN)< 1.5 V
Performance IconPerformance
output response time (high speed)200 µs
output response time (standard)500 µs
repeatability (high speed)66 µs
repeatability (standard/long range/extra long range)100 µs
Operating Environment IconOperating Environment
operating temperature−10 °C to +55 °C
storage temperature−20 °C to +85 °C
humidity90% at +60 °C maximum relative humidity (non-condensing)

Related product manuals