14 Assembly and operating instructions / EN
8. Commissioning
In the application documents, the running meters of the SCR
sensor cable and/or the PS point sensor, or PSO, which are
monitored by the RLA
net
, should be given, e.g. shown on a
blueprint or on a general site map.
The countermeasures that are initiated when a leak is reported
must be adapted to the damage to be avoided in terms of scope
and reaction speed. The owner/management company must find
out about the requirements from the respective insurance
company (building insurance, liability insurance), e.g. test
intervals, scope of testing and training of operating personnel.
The commissioning report in Chapter 16.2 must be filled out
during commissioning and attached to the system documentation.
Check sensor cable and point sensors
According to the test report - see Chapter 16.1
Warranty claims can only be asserted by submitting a correctly
and completely filled out acceptance report. The form must also
be dated and signed.
9. The service programme
The “RLA_net_com” programme is the software communication
interface of the RLA
net
monitoring device and is displayed on a
PC. In this programme the user can set the basic parameters of
the RLA
net
and the application parameters of the connected
sensors and upload them to the RLA
net
.
Changes to the set values can be made with the service
programme.
Factory preset values of the RLA
net
are suitable for the first start-
up of the monitoring function of the leakage detection system. For
the correct localisation of the leakage, the application data must
be adapted to the local situation and the installed system.
Factory preset values for process representation and
parameterisation: The data is available in the MODBUS RTU
protocol. A detailed description can be found in Chapter 9.3
Setting the sensor parameters.
ATTENTION!
Warning regarding the incorrect setting of
RLA
net
parameters
If the RLA_net_com programme is run in online
mode, important parameters of the connected
RLA
net
may change. This can affect the operational
reliability of the entire water detection system. Only
trained technical personnel are allowed to run the
RLA_net_com program in online mode.