22 Assembly and operating instructions / EN
11. Operation
The installed system can be monitored for leaks while the RLA
net
is in operation. A prerequisite is that the system has been
professionally installed and commissioned. The RLA
net
shows the current operating status of the system on the device and the
software.
The product service life of the RLA
net
is designed to last for more than 10 years.
The product is suitable for permanent use and is maintenance-free.
In the event of a fault or leakage, first check the function of the downstream equipment.
The table below shows some fault events, their cause or effect and the measures to be taken.
Fault
Cause
Effect/ measures
Leak, but
location is dry
Multiple leaks
present at the
same time
The nearest leak is
displayed / read out the
error memory, check all
localisation points
Leak comes
and goes
Condensing
humidity
Dew point reached under
insulation / read out fault
memory, dry and seal
insulation
Service
message
comes and
goes
Faulty
contacting in the
wiring
Line break / read error
memory, check all clamp
and plug connections

Questions and Answers: