ATTENTION!
Warning of unresolved leakage
The RLA
net
is reset by pressing the Confirm leakage
button. The error message in the display is deleted.
It is necessary to check the system for existing
leaks! If necessary, arrange for the cause of the leak
to be eliminated.
The Confirm leakage button should only be used by
the service personnel responsible for
troubleshooting and repairs.
9.6. Viewing the event log
Software area Record
The RLA
net
stores up to 32 events in its memory. All other events are not saved.
These stored events can be called up using the "Read record" button.
The memory can be cleared by clicking on the "Clear record" button.
PLEASE NOTE!
Risk of data loss
Do not delete information about leaks and system
malfunctions in general. This information can
provide important information to service technicians.
The report can only be displayed when the service programme's monitoring mode is ended, i.e. the "Stop Monitor" button in the Monitor
software area has been pressed.

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Bartec RLAnet 17-85G5-2123 Series and is the answer not in the manual?

Bartec RLAnet 17-85G5-2123 Series Specifications

General IconGeneral
BrandBartec
ModelRLAnet 17-85G5-2123 Series
CategoryMeasuring Instruments
LanguageEnglish

Related product manuals