EasyManua.ls Logo

Basler DECS-250 - Page 119

Basler DECS-250
374 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
9440300990 14-3
DECS-250 Event Recorder
• Cross-current compensation enabled or disabled
• Grid Code enabled or disabled
• APC enabled or disabled
• LFSM enabled or disabled
• LVRT mode enabled or disabled
• Test mode enabled or disabled
Mode trigger settings are illustrated in Figure 14-3.
Figure 14-3. Data Log Mode Triggers
Level Triggers
Level triggering initiates a data log based on the value of an internal variable. The variable can be a
minimum or maximum value and can be specified to trigger a record when the monitored variable crosses
a minimum threshold from above, or a maximum threshold from below. A minimum and maximum
threshold may also be selected for the monitored variable, causing the monitored value to trigger a record
when it rises above its maximum threshold or decreases below its minimum threshold.
Level triggers are configured in BESTCOMSPlus on the Level Triggers tab (Figure 14-4) in the Data Log
area of the Report Configuration. The Level Triggers tab consists of a list of parameters that can be
selected to trigger a data log. Each parameter has a level trigger enable setting which configures
triggering of a data log when the parameter increases above the upper threshold setting or decreases
below the lower threshold setting. The parameters available to trigger a data log are listed below.
Figure 14-4. Data Log Level Triggers
• APC desired reference
• APC error
• APC output
• APC state
• Auxiliary voltage input
• AVR output
• AVR PID error signal input
• Bus frequency
• Bus voltage
• Comp. frequency deviation
• Control output
• Cross current input
• Droop
• FCR error
• FCR output
• FCR state
• Field current
• Field voltage
• Frequency response
• FVR error