21-14 9440300990
BESTlogicâ„¢Plus DECS-250
Name Description Symbol
AUTO TRANSFER
ENABLE
When true, this element sets the unit as
secondary. When false, the unit is primary.
CROSS CURRENT
COMPENSATION
DISABLE
When true, this element disables cross
current compensation.
DATALOG LOGIC
STATUS
When true, Logic Status x can be selected
and displayed in the data log and the real-
time monitor.
DATALOG TRIGGER When true, this element triggers the datalog
to begin recording data.
DROOP DISABLE When true, this element disables droop when
the unit is operating in AVR mode.
EXTERNAL
TRACKING DISABLE
When true, this element disables external
tracking.
FREEZE APC
OUTPUT
When true, the output of the APC PI controller
is frozen.
This can be used with the APC REMOTE
COMM FAIL status input to freeze APC
output when remote communication fails.
FREEZE LVRT
OUTPUT
When true, the output of the LVRT controller
is frozen.
This can be used with the LVRT REMOTE
COMM FAIL status input to freeze LVRT
output when remote communication fails.