9440300990 29-29
DECS-250 PROFIBUS Communication
Instance Name
Inst. #
Type
RW
Key Name
Unit
Range
Bus Condition Detection
(Gen Sensing)
158
Float
R/W
Gen Stable Alternate
Frequency
Scale Factor GG
No Unit
0.001 - 100
Bus Condition Detection
(Bus Sensing)
160
Float
R/W
Dead Bus
Threshold GG
V
0 - 600000
Bus Condition Detection
(Bus Sensing)
160
Float
R/W
Dead Bus
Time Delay GG
Sec
0.1 - 600
Bus Condition Detection
(Bus Sensing)
160
Float
R/W
Bus S table
Over Voltage
Pickup GG
V
10 - 600000
Bus Condition Detection
(Bus Sensing)
160
Float
R/W
Bus Stable
Over Voltage
Dropout GG
V
10 - 600000
Bus Condition Detection
(Bus Sensing)
160
Float
R/W
Bus Stable
Under Voltage
Pickup GG
V
10 - 600000
Bus Condition Detection
(Bus Sensing)
160
Float
R/W
Bus Stable
Under Voltage
Dropout GG
V
10 - 600000
Bus Condition Detection
(Bus Sensing)
160
Float
R/W
Bus Stable
Over Frequency
Pickup GG
Hz
46 - 64
Bus Condition Detection
(Bus Sensing)
160
Float
R/W
Bus Stable
Over Frequency
Dropout GG
Hz
46 - 64
Bus Condition Detection
(Bus Sensing)
160
Float
R/W
Bus Stable
Under Frequency
Pickup GG
Hz
46 - 64
Bus Condition Detection
(Bus Sensing)
160
Float
R/W
Bus Stable
Under Frequency
Dropout GG
Hz
46 - 64
Bus Condition Detection
(Bus Sensing)
160
Float
R/W
Bus Stable Activation
Delay GG
Sec
0.1 - 600
Bus Condition Detection
(Bus Sensing)
160
Float
R/W
Bus Failed Activation
Delay GG
Sec
0.1 - 600
Bus Condition Detection
(Bus Sensing)
160
Float
R/W
Bus Stable Low Line
Scale Factor GG
No Unit
0.001 - 3
Bus Condition Detection
(Bus Sensing)
160
Float
R/W
Bus Stable Alternate
Frequency Scale
Factor GG
No Unit
0.001 - 100
Governor Bias Control
161
UINT32
R/W
Control Contact
Type GG
No Unit
Continuous=0 Proportional=1
Governor Bias Control
162
Float
R/W
Correction Pulse
Width GG
Sec
0 - 99.9
Governor Bias Control
162
Float
R/W
Correction Pulse
Interval GG
Sec
0 - 99.9
Gen Undervoltage
163
UINT32
R/W
Mode PP
No Unit
Disabled=0 Enabled=1
Gen Undervoltage
163
UINT32
R/W
Mode PS
No Unit
Disabled=0 Enabled=1
Gen Undervoltage
164
Float
R/W
Pickup PP
V
1 - 600000
Gen Undervoltage
164
Float
R/W
Time Delay PP
ms
100 - 60000
Gen Undervoltage
164
Float
R/W
Pickup PS
V
1 - 600000
Gen Undervoltage
164
Float
R/W
Time Delay PS
ms
100 - 60000
Gen Undervoltage
165
UINT32
R/W
Mode PP
No Unit
Disabled=0 Enabled=1
Gen Undervoltage
165
UINT32
R/W
Mode PS
No Unit
Disabled=0 Enabled=1
Gen Undervoltage
166
Float
R/W
Pickup PP
V
0 - 600000
Gen Undervoltage
166
Float
R/W
Time Delay PP
ms
100 - 60000
Gen Undervoltage
166
Float
R/W
Pickup PS
V
0 - 600000
Gen Undervoltage
166
Float
R/W
Time Delay PS
ms
100 - 60000
Loss of Sensing
167
UINT32
R/W
Mode GG
No Unit
Disabled=0 Enabled=1
Loss of Sensing
167
UINT32
R/W
Sys Option No Sense To
Manual Mode GG
No Unit
Disabled=0 Enabled=1