EasyManua.ls Logo

Beijer Electronics BFI-H3 - Fieldbus Control Settings; Fieldbus Communication Protocol

Beijer Electronics BFI-H3
32 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Beijer Electronics Frequency Inverter BFI-H3 KI00363D 2021-07
www.beijerelectronics.com 16 (32)
5.6 Fieldbus control settings
The drive can be controlled by fieldbus or Ethernet. Following settings must be done:
P1-12=4, Start/stop/frequency setpoint command by bus
P1-14=201, make access to parameters in group 5 mentioned below
Terminal 2 must be connected to 24 V and safety inputs(STO+/STO-) correctly connected.
Specific details
Station-
number
Fieldbus
ramp
action P5-
07
Communication
Speed/Baud
rate
Timeout [sec]
P5-05
Loss action
P5-06
ProfiNet
GSDML-V2.25-HMS-
ABCC-PRT2P-
201110111.xml
Set by
master
0: Ramp
time by
parameter
1: Ramp
time sent by
serial,
fieldbus or
Ethernet
Set by master
Drive behaviour if
a communication
command is not
received within
time specified in
this parameter.
Type of reaction
decided in P5-06.
0: Trip
1: Ramp to
stop and
trip
2: Ramp to
stop and
no trip
3: Preset
speed 8
(P2-08)
Profibus DP
HMSB1811.gsd
P5-01
EtherNet/IP
Set manually
by PC-program
Modbus TCP
CC-Link
Ver1, Remote device
station, Exclusive
station 2
P5-01
P5-03:
9,6= 156 kbs
19,2= 625 kbs
38,4= 2,5 Mbs
57,6= 5 Mbs
115= 10 Mbs
Ethercat
Contact Beijer support
for latest version
Set by
master
Set by master
DeviceNet
005A000000620200.
eds
P5-01
P5-03
5.7 Fieldbus communication protocol
Cyclic data for all bus types consist of four 16-bit word input and output. Word 1 and 2 has
the following meaning:
Word
Data to drive
Data from drive
1
Bit 0
0: Stop
1: Start
Bit 0
0: Stop
1: Startsignal on
Bit 1
0: Deceleration time in P1-04
1: Deceleration time in P2-25
Bit 1
0: Drive Healthy
1: Drive tripped
Bit 2
0: No function
1: Alarm reset
Bit 2
0: Auto Mode
1: Hand mode
Bit 3
0: No function
1: Coasting stop
Bit 3
0: Safe Torque inputs activated
1: Safe Torque inputs deactivated
Bit 4-
15
Not used
Bit 4
0: Maintenance not required
1: Maintenance required
Bit 5
1: In Standby or Sleep mode
Bit 6
1: BFI Ready to run. Software enable, power on, AUTO
mode, STO ok and no active alarm.
Bit 7
1: Low or High Load detected
Bit 8-15
Alarmcode
2
Set frequency [0,1 Hz]
Actual output frequency [0,1 Hz]

Related product manuals