Beijer Electronics Frequency Inverter BFI-H3 KI00363D 2021-07
www.beijerelectronics.com 21 (32)
0: 0-10 V 3: 0-20 mA 4: t 4-20 mA, trip if signal is below 3 mA
5: r 4-20 mA, ramp to Preset Speed4, P2-04, if signal is below 3 mA.
(Setpoint value–Feedback value) of PID controller multiplied by P3-01 to
produce output from PID controller.High value cause instability.
Accumulated error in the PID control between (Setpoint value–Feedback
value) to influence the output from PID controller. P3-02 is time constant.
Larger values provide damped response. Lower values result in a faster
system response but may result in instability. 0= Turned off
The Differential time constant references the rate of change of the
feedback signal over time and works to slow the rate of change of the PID
controller, particularly as it approached the set-point. Shorter time will
decrease overshoot but slow down response and may lead to instability.
0= Turned off.
0: Direct Operation. Increase of motor speed increase feedback signal
1: Inverse Operation. Increase in motor speed should decrease feedback
signal
PID Digital Reference
source
0: PID-reference in P3-06
1: Analog reference on terminal 6
PID–reference: 0-100 % of PID-feedback signal if P3-06=0
Maximum output frequency in % of P1-01
Minimum output frequency in % of P1-01
0 : Analog Input 2 (Terminal 10)
0: Internal ramps are always used.
0,1-100: When PID-error is less than setting internal ramps are not used
and PID–controller ramps output frequency. Drive can react quickly to
small errors.
Extra special PID functions
Scaling factor of displayed PID feedback. If analog input is 0–10 V(=0-
100%) and is equal to 0-10 bar pressure setting is 0,1.
PID Sleep mode parameters. P3-14 defines output frequency at which the
drive will enter standby mode (stop). Drive enters standby mode if motor
speed remains below level in P3-14 for time period in P2-27. Display will
show Standby. Function disabled if P2-27=0.
PID Wake up level. When PID error > P3-13 drive will restart motor.
2nd PID Digital Reference
Second PID reference activated by a digital signal.
≠ 0: Burst pipe protection function enabled.
If PID feedback, when starting motor, is not > P3-17 within time P3-16 the
drive will trip with "Pr-Lo" (pressure low trip).
% of PID feedback signal. See P3-16.
Burst Pipe Detection Trip
Delay
Delay/filtering false trip due to overshoot or undershoot of sensor signal.
For instance pressure shocks due to valves going on and off.
0: PID loop will continue running as long as P gain (P3-01) ≠ 0.
1: PID loop will only run when drive is enabled. If drive is not running, PID
output will reset to 0 (Including integral result).
Drive can be started with speed in P2-07 without PID active. When time
from start in P6-11 has elapsed the drive enters automaticall PID-control.
If PID-control is to be performed by serial, Fieldbus or Ethernet, contact Beijer Electronics.