Beko BEHPH 090 - Warning for Using R32;R290 Refrigerant

Beko BEHPH 090
228 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
10 / 172 EN
Split Type Air Conditioner / User Manual
4. For equipment that contains
fluorinated greenhouse gases
in quantities of 5 tonnes of
CO2 equivalent or more, but
of less than 50 tonnes of
CO2 equivalent, If the system
has a leak-detection system
installed, it must be checked
for leaks at least every
24 months.
5. When the unit is checked for
leaks, proper record-keeping
of all checks is strongly
recommended.
Warning for Using R32/R290
Refrigerant
• When flammable refrigerant
are employed, appliance shall
be stored in a well -ventilated
area where the room size
corresponds to the room area
as specific for operation.
For R32 frigerant models:
Appliance shall be installed,
operated and stored in a room
with a floor area larger than
4m
2
.
1 Safety Precautions
For R290 refrigerant models,
appliance shall be installed,
operated and stored in a room
with a floor area larger than:
<=9000Btu/h units: 13m
2
>9000Btu/h and
<=12000Btu/h units: 17m
2
>12000Btu/h and
<=18000Btu/h units: 26m
2
>18000Btu/h and
<=24000Btu/h units: 35m
2
• Reusable mechanical
connectors and flared joints
are not allowed indoors. (EN
Standard Requirements).
• Mechanical connectors used
indoors shall have a rate of
not more than 3g/year at 25%
of the maximum allowable
pressure. When mechanical
connectors are reused indoors,
sealing parts shall be renewed.
When flared joints are reused
indoors, the flare part shall be
re-fabricated. (UL Standard
Requirements)