56 / 172 EN
Split Type Air Conditioner / User Manual
Model name
Indoor unit BEVPI 090 BEVPI 120 BEVPI 180 BEVPI 240
Outdoor unit BEVPI 091 BEVPI 121 BEVPI 181 BEVPI 241
Noise Pressure Level - Indoor Unit (dBA)
56 55 57 63
Noise Pressure Level - Outdoor Unit (dBA)
63 63 65 67
Air flow volume (m
3
/h)
416/309/230 584/477/395 730/500/420 1020/830/640
Rated Power Input-EN 60335(W)
2150 2150 2500 3700
Rated Current Input-EN 60335(A)
10 10 13 19
Indoor unit Resistance Class
IPX0 IPX0 IPX0 IPX0
Outdoor unit Resistance Class
IP24 IP24 IP24 IP24
High Pressure Pipe Diameter (mm)
6.35mm (1/4in) 6.35mm (1/4in) 6.35mm (1/4in) 9.52mm (3/8in)
Low Pressure Pipe Diameter (mm)
9.52mm (3/8in) 9.52mm (3/8in) 12.7mm (1/2in) 15.9mm (5/8in)
Power Supply Cord specification (mm
2
)
1.5x3 1.5x3 1.5x3 2.5x3
Indoor & Outdoor Connection Cord (mm
2
)
1.5x5 1.5x5 1.5x5 2.5x5
Max. elevation (m)
10 10 20 25
Max. pipe length (m)
25 25 30 50
Additional Gas Quantity (g/m)
12 12 12 24
Indoor Unit (WxHxD) mm
752×290×219 832×297×223 995×319×251 1119×336×259
Outdoor Unit (WxHxD) mm
720x495x270 720x495x270 805x554x330 890x673x342
Indoor Unit Net Weight (kg)
8.5 9.5 12 15
Outdoor Unit Net Weight (kg)
23 23 32 43
Note:
1. Specifications are standard values calculated based on rated operating conditions, They will vary in
difference work condition.
2. Our company has quick technical imporvments. There will be prior notice for any change of technical
data. Please read nameplate on the air-conditioner.
Please refer to detail product information required in Regulation No 206/2012 from leaflet of Product
Fiche.