EasyManua.ls Logo

Belimo NMV-D2M - Page 41

Belimo NMV-D2M
48 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
41
4A1PC-T V2.1 NMV-D2M-EN 11-02-04.doc PM VAV - Subject to technical changes
VAV Module NMV-D2M
Legend
Sequence
a) Step 1: V’max
- Volumetric flow at setpoint
- Damper control range ~42%
b) Step 3: V’min
- Volumetric flow at setpoint
- Damper control range ~28%
N-P1.5 VAV- / CAV-Box
.........................................................................
excessive system supply pressure
Suggestion for optimising
Set the fan and pressure control so that the damper
position of the VA-V/ CAV-boxes in V’max opera
tion is
approximately 80%
Suitable Test-Sequences
- BasicTest Max-Min 5m.txt
Cause
Fan or pressure control rated too high or set up too
high.
a
b
S
A
D
A
Suggestion for a remedy
- Increase the operating flow rate setting so that the
V’min volumetric flow setting corresponds to an ac-
tive differential pressure setting of more than 2 Pa.
- Investigate changing the air box (smaller nominal
diameter).
N-P1.6 VAV- / CAV-Box
.............................................................................................................
oversized air unit
Sequence
a) The setpoint is reduced in 1% steps
b) - Setpoint less than active differential pressure
2 Pa
- NMV-D2M function
Leakage-flow suppression activated
c) - Setpoint less than active differential pressure
2 Pa
- Actual volumetric flow rate = 0
Suitable Test-Sequences
- Test 5 Max-Min-Max [1%] 37m.txt
- Test 4 Max-Mid-Min 9m.txt
Note:
If the system does not attain the required supply pressure during the
Test start the Test-Sequence is discontinued and the fault alarm ‘In-
adequate supply air pressure’ is given.
See:
- Air box manufacturer’s documentation on minimum air flow for the VAV-/CAV-
box
- section ‘N-S1.2.1 Control range’
Causes and consequences
- VAV-/CAV-box oversized for the required value of
volumetric flow
- Oversized air boxes are being operated in a difficult-
to-control, sometimes uncontrollable, range
- The function range of the VAV-/CAV-box must not
exceed 2 Pa. Otherwise the air box will be operated
near leakage-flow suppression, i.e. in the uncontrol-
lable range.
a
b
c
S
A
D
A
NMV-D2M Diagnosis
Legend

Related product manuals